Description
Product Overview
GE IS200BPPBH2CAA (BPPB) is the BOP (Balance of Plant) processor board for GE Speedtronic Mark VI / Mark VIe gas & steam turbine control systems. It executes auxiliary plant control logic, analog signal acquisition processing, interlock and alarm handling for balance-of-plant equipment including lube oil systems, cooling water, drains and auxiliary valves. It communicates with the main turbine controller and field terminal boards to monitor auxiliary equipment status and execute plant auxiliary protection sequences. Widely used in combined cycle power plants, gas turbine and steam turbine facilities, it is a critical legacy spare for maintenance and retrofit of Mark VI/Mark VIe turbine control racks.
Technical Specifications
| Parameter | Details |
|---|---|
| Part Number | IS200BPPBH2CAA |
| Brand | GE General Electric |
| Type | BOP Processor Board (BPPB) |
| Compatible Platform | GE Speedtronic Mark VI / Mark VIe Turbine Control |
| Form Factor | Single slot VME PCB card |
| Communication | Backplane Corebus, high-speed link to main controller and I/O terminal boards |
| Signal Interface | Interfaces with analog and discrete terminal boards for BOP field sensors |
| Watchdog | Hardware watchdog for fault detection and safe failover |
| Front Indicators | Dual LED indicators for power, run status and fault alarm |
| Conformal Coating | Acrylic conformal coating for dusty, humid cabinet environments |
| Operating Temperature | -30°C ~ +65°C |
| Storage Temperature | -40°C ~ +85°C |
| Humidity | 5~95% RH, non-condensing |
| Mounting | Plug-in VME slot inside Mark VI/VIe control rack |
| Net Weight | ~0.46 kg |
| Certifications | CE |
| Product Status | OEM discontinued, aftermarket spare only |
Key Features
- Dedicated BOP processor for auxiliary plant control logic separate from turbine main control
- Real-time processing for lube oil, cooling system and auxiliary valve interlocks and alarms
- Hardware watchdog circuit to detect processor failure and trigger safe fault response
- Backplane Corebus communication for data exchange with main CPU and I/O terminal boards
- Conformal coated PCB for high vibration and corrosive power plant cabinet environments
- Front panel LED indicators for fast on-site status and fault diagnosis
- Supports TMR triple redundant architecture for high availability turbine auxiliary protection
Installation & Testing Notes
- Insert IS200BPPBH2CAA into dedicated VME slot of Mark VI / Mark VIe control rack
- Confirm backplane connectors are fully seated; verify cabinet grounding before power energization
- After power-up, check front LED status and run built-in self-test via turbine HMI
- Verify BOP interlock logic, analog measurements and auxiliary equipment alarm functions
- This board does NOT support hot swap. Isolate rack control power before removal
- After replacement, perform full BOP logic simulation and interlock test
- Periodically inspect connector tightness in high vibration turbine cabinet environments
FAQ
Q: What system is IS200BPPBH2CAA used for? A: GE Speedtronic Mark VI / Mark VIe gas and steam turbine control system.
Q: What does BPPB stand for? A: BOP Processor Board, dedicated to Balance of Plant auxiliary control functions.
Q: What is the main function of this board? A: It runs auxiliary plant control logic for lube oil, cooling water and auxiliary valve interlocks and alarms.
Q: Is IS200BPPBH2CAA hot swappable? A: No, rack control power must be shut down before removing or installing the board.
Q: What type of PCB coating is applied? A: Acrylic conformal coating to protect against dust, humidity and corrosive atmosphere.