Sale!

Yokogawa AAT141-S00 DCS FIO Thermocouple & RTD Analog Input Module

Original price was: $3,577.00.Current price is: $3,566.00.

Item Parameter
Part Number AAT141-S00
Module Type TC/mV/RTD Temperature Input Module
Applicable System Yokogawa CENTUM VP FIO node
Number of Channels 16 isolated channels, per-channel signal type configuration
Supported Input TC (K,J,E,B,R,S,T,N), mV (-100~150mV / -20~80mV), 3-wire Pt100 RTD
Input Impedance ≥2MΩ
Withstand Voltage 1500V AC between field side and system side, 1 minute
Accuracy TC: ±30μV; mV: ±80μV(-100~150mV), ±30μV(-20~80mV); RTD: ±120mΩ
Cold Junction Compensation Built-in, compensation accuracy ±1°C
Category: SKU: AAT141-S00 Tag: Brand:

Description

Product Overview

Part Number: AAT141-S00 Manufacturer: Yokogawa (Yokogawa Electric, Japan) Product Series: CENTUM VP DCS, FIO Field I/O Module Type: TC/mV/RTD Multi-type Temperature Input Module AAT141-S00 is a 16-channel fully isolated temperature & millivolt input module for Yokogawa CENTUM VP FIO nodes. It supports flexible mixed signal acquisition: thermocouple (TC), millivolt (mV) and 3-wire Pt100 RTD. Each channel can be independently configured for different sensor types. Built-in cold junction compensation for thermocouple measurement. It converts weak field temperature signals into digital data and communicates with FCS controller via ESB bus. Widely used in petrochemical, power, oil & gas and chemical plants for furnace, reactor and pipeline temperature monitoring. Supports hot swap and dual-redundant installation.

 

Technical Specifications

Item Parameter
Part Number AAT141-S00
Module Type TC/mV/RTD Temperature Input Module
Applicable System Yokogawa CENTUM VP FIO node
Number of Channels 16 isolated channels, per-channel signal type configuration
Supported Input TC (K,J,E,B,R,S,T,N), mV (-100~150mV / -20~80mV), 3-wire Pt100 RTD
Input Impedance ≥2MΩ
Withstand Voltage 1500V AC between field side and system side, 1 minute
Accuracy TC: ±30μV; mV: ±80μV(-100~150mV), ±30μV(-20~80mV); RTD: ±120mΩ
Cold Junction Compensation Built-in, compensation accuracy ±1°C
Max total wiring resistance ≤1000Ω
Redundancy Dual redundant support
Hot Swap Yes, online replacement
Power Supply 5VDC from FIO node backplane
Operating Temperature 0°C ~ +50°C
Storage Temperature -20°C ~ +70°C
Humidity 5~95% RH, non-condensing
Weight Approx 300g

 

Engineer Notes

  1. AAT141-S00 belongs to FIO series I/O module for CENTUM VP, not compatible with old CS3000 system.
  2. Supports mixed sensor configuration, each of the 16 channels can be separately set to TC, mV or Pt100.
  3. Built-in cold junction compensation eliminates external reference junction box for thermocouple application.
  4. Supports sensor burnout detection, can trigger alarm when thermocouple or RTD sensor wire is broken.
  5. Can be installed as dual redundant pair; automatic switchover upon module fault without interrupting temperature data acquisition.
  6. Hot-swap function allows module removal and replacement while DCS online, no system shutdown required.
  7. Use matched Yokogawa ATT4S / ATT4D terminal boards for field wiring; shielded twisted-pair cable is strongly recommended for weak temperature signals to reduce noise.
  8. Check module LED indicators for power, ESB communication and channel fault status during commissioning and routine maintenance.

 

Pre-Shipment Test Protocol

  1. Power-on self-test and LED status verification
  2. Multi-type sensor calibration test: TC, mV and Pt100 RTD full range accuracy test
  3. Sensor burnout detection function verification
  4. Redundancy switchover simulation test
  5. Channel isolation & insulation resistance inspection
  6. Continuity test of internal circuit
  7. Visual inspection of housing, connectors, label and marking
  8. Anti-static & shockproof packaging inspection

 

Buyer FAQ

Q: Is AAT141-S00 new original? A: We supply brand new original Yokogawa units, 12-month warranty, factory test certificate available on request.

Q: What does suffix S00 mean? A: S = standard type; 00 = basic non-explosion-proof version for FIO node.

Q: What is the difference between AAT141-S00 and AAR181-S50? A: AAT141-S00:16 channels, supports TC/mV/Pt100 mixed input. AAR181-S50:12 channels, only for Pt100 RTD.

Q: Can AAT141-S00 work in redundant configuration? A: Yes, two AAT141-S00 modules can be configured as dual redundant pair with ATT4D redundant terminal block.

Yokogawa EC401-50 DCS FIO Node Bus Coupler Industrial Automation Card
Yokogawa AAI143-H50 DCS FIO Analog Input Module with HART Function
Yokogawa AAI543-H50 DCS FIO AO Module with HART Function
Yokogawa AAR181-S50 DCS FIO RTD Temperature Input Module