Description
Product Overview
1KGT036500R0001 (Alias: 560AIR01 R0001) is an ABB high-precision 8-channel analog input module designed for power plant turbine and generator control systems. It acquires analog current and voltage signals from field transmitters, sensors and transducers, converts raw analog signals into digital data for the controller. The module supports bipolar and unipolar signal ranges, features 12-bit plus sign resolution, and delivers reliable measurement for critical power process variables.
Technical Specifications
| Item | Parameter |
|---|---|
| Manufacturer | ABB |
| Part Number | 1KGT036500R0001, 560AIR01 R0001 |
| Product Type | 8-Channel Analog Input Module |
| Resolution | 12 bit + sign |
| Input Signal Ranges | ±2mA, ±5mA, ±10mA, ±20mA, ±40mA; ±2VDC, 0~20VDC |
| Number of Channels | 8 isolated analog input channels |
| Power Supply | Backplane powered |
| Mounting | Rack slot plug-in module |
| Operating Temperature | -20 °C ~ +60 °C |
| Humidity | 5%–95% RH non-condensing |
| Net Weight | 0.125 kg |
| Country of Origin | Poland |
Key Features
- Multi-Range Analog Signal Acquisition: Supports multiple mA and DC voltage input ranges to interface with pressure, temperature, vibration and rotor angle transducers widely used in power generation.
- 12-bit+Sign High Resolution Conversion: Delivers accurate analog-to-digital conversion for high-precision turbine and generator measurement applications.
- 8 Independent Input Channels: Each channel can be individually configured for different signal types to reduce spare module variety.
- Built-in Channel Diagnostics: Continuously detects open circuit, short circuit and out-of-range signal faults, reporting diagnostic status to the host controller.
- Electrical Channel Isolation: Provides isolation between field side analog signals and internal control backplane to mitigate noise and surge interference.
- Compact Rack Mount Design: Slim form factor for installation in ABB power control racks, optimized for turbine/generator auxiliary control cabinets.
Applications
- Thermal and combined-cycle power plant turbine control systems
- Generator protection and excitation monitoring signal acquisition
- Hydroelectric plant control and measurement racks
- Captive power station critical analog signal monitoring
- Vibration, temperature and pressure transducer signal interface
Installation & Maintenance Notes
- ESD protection is mandatory during handling and module replacement.
- Verify each channel signal range configuration before applying field transducer wiring.
- Separate analog signal cables from high-current power and ignition wiring to avoid EMI.
- Perform channel calibration check during scheduled unit outages.
- Review module diagnostic fault logs in engineering software for broken wires or transducer failures.
- Confirm backplane connector seating and secure terminal block connections after installation.
FAQ
Q: What is the alias name of 1KGT036500R0001? A: Its commercial alias is 560AIR01 R0001, both references point to the identical 8-channel analog input module.
Q: Can this module read 4-20mA transmitter signals? A: Yes, it supports ±20mA input range and can be configured for standard 4–20mA field transmitters.